4-89
Group 01-V/F Control Parameters
01- 00
V/F Curve Selection
Range
0~FF
When restore factory setting (13-08), this parameter will not be changed.
The V/F curve selection is enabled for V/F mode. Make sure to set the inverter input voltage parameter
01-14.
There are three ways to set V/F curve:
(1) 01-00 = 0 to E: choose any of the 15 predefined curves (0 to E).
(2) 01-00 = 0F, use 01-02~01-09 and 01-12 ~ 01-13, with voltage limit.
(3) 01-00 = FF: use 01-02~01-09 and 01-12 ~ 01-13, without voltage limit.
The default parameters (01-02 ~ 01-09 and 01-12 ~ 01-13) are the same when 01-00 is set to F (default)
and 01-00 is set to 1.
Parameters 01-02 ~ 01-13 are automatically set when any of the predefined V/F curves are selected.
This parameter will be affected to reset by the initialization parameter (13-08).
Consider the following items as the conditions for selecting a V/F pattern.
(1) The voltage and frequency characteristic of motor.
(2) The maximum speed of motor.