4-140
The maximum output voltage will be limited by 01-03, Vmax = 100%
Figure 4.4.32 Bias adjustment
04-05/04-10=4: Acceleration and deceleration coefficient (K)
Multi-function analog input AI2/AI3 can be used to adjust the acceleration and deceleration time coefficient.
The actual acceleration and deceleration time is calculated as follows:
Acceleration / Deceleration time (00-14 ~ 00-17, 00-21~ 00-24)
Actual accel /decel time =
K
Acceleration/ Deceleration time setting is 100% (00-14~00-17, 00-21~00-24).
Figure 4.4.33 Acceleration / deceleration time reduction coefficient
04-05/04-10=5: DC braking current
Multi-function analog input AI2/AI3 can be used to adjust the DC Injection braking current.
DC braking current parameter 07-07 setting should be set to 0% to use this function.
The inverter rated current = 100%
Note: When using the permanent magnet (PM) motor, there will be no options of setting 5.