Figure 4.4.43 Periodic automatic operation
Example 3: Automatic operation mode – Single cycle and continue running at last speed of the cycle
In this example the inverter executes a single cycle and continue running at last speed of the cycle.
Figure 4.4.44 Single cycle automatic operation (continuous)
06-00= 1 to 3:
After a stop the inverter will start with the incomplete step when the run command is re-applied.
06-00= 4 to 6:
After a stop the inverter will start with the first step of the cycle when the run command is re-applied.
Notes:
- Acceleration/ deceleration time is set with parameters 00-14 and 00-15 in automatic operation mode.
- If the setting value of parameters 06-16~06-31 is 0, automatic operation mode is not active.