EasyManua.ls Logo

TECO F510 series - Page 253

TECO F510 series
555 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-164
07- 13
Low Voltage Detection Level
Range
200V: 150~300V
400V: 300~600V
07- 25
Low voltage Detection Time
Range 0.00~1.00Sec
Adjust the 07-13 voltage level from 150 to 300 Vdc (200V class) or from 300 to 600 Vdc (400V class).
When the AC input voltage is lower than the 07-13 value (07-13/ 1.414 = AC voltage detection level) for
the time specified in 07-25 the low-voltage error "UV" will displayed. If 07-25 = 0.00 sec., the UV error will
be displayed immediately.
Set preventive measures:
- The inverter input voltage will limit the output voltage. If the input voltage drops excessively, or if the
load is too big, the motor may stall.
- If the input voltage drops below the value set in 07-13 then the output is turned off momentarily. The
inverter will not automatically start when power is restored.
07- 14
Pre-excitation Time
Range
0.00~10.00Sec
07- 15
Pre-excitation Level
Range
50~200%
If a high starting torque is required for the application, especially for a large horsepower motors, the
pre-excitation operation can be used to pre-flux (magnetize) the motor.
07-14: Pre-excitation time
When an operation command (forward or reverse) is activated, the inverter will automatically start
pre-excitation based on the time set in parameter 07-14.
The time for the flux to reach 100% is a function value of motor’s electrical time constant (See figure
4.4.52).
Electrical time constant (quadratic by-pass circuit time constant) is suggested to set 2.00~4.00 Sec.
07-15: Pre-excitation initial level
Use the pre-excitation initial level (07-15) to provide a higher excitation current during the pre-excitation
time (07-14), which will increase the speed and stability for motors.
In order to quickly magnetize the motor, reduce the pre-excitation time (07-14) and set the pre-excitation
level (07-15) to a high level.
If 07-15 is set greater than 100%, providing a high excitation current during the pre-excitation time (07-14),
motor’s magnetization time is shorted. When the setting reaches 200%, magnetization is reduced by
roughly half.
A high pre-excitation level (07-15) might result in excessive motor sound during pre-excitation.
When the flux reaches 100%, pre-excitation current reverts back to 100% and pre-excitation is completed.

Table of Contents

Other manuals for TECO F510 series

Related product manuals