Loading...
4-183
08 - 46
Temperature agree level
Range
0 ~ 254°C
08 - 47
Temperature reset level
Range
0 ~ 254°C
Note: 08-47 maximum value will be limited by 08-46 set value
The inverter temperature agree and reset level selection
03-11 set to59:
08-46: The inverter temperature is > 08-46, the relay operates.
08-47: When the output current is 08-47, the relay signal from ON to OFF.
Down time frequency diagram:
08-46
03-11
繼電器
ON
變頻器溫度
T(°C)
Time
08-47
Inverter temperature agree and reset detection
08 - 48
Selection of Fire Mode
Range
0: Disable
1: Enable
08 - 49
Multi-Function Input Terminal Status of Fire Mode
Range
0: Reset after Power Off
1: Reset after Terminal Removed
08 - 50
Multi-Function Terminal Status of Fire Mode
Range
xxx0b: S6 A Contact
xxx1b: S6 B Contact
08 - 51
Motor Speed Setting Source of Fire Mode
Range
0】:Fire Mode Speed (08-52)
1】:PID Control
2】:AI2
08 - 52
Fire Mode Motor Speed
Range
0.00~100.00%
08 - 59
Fire Mode Motor Direction
Range
0: Forward
1: Reverse
08 - 60
Fire Mode Password
Range
00000 ~ 65534
When 08-48=0, Fire Mode is disabled.