4-185
08 – 59: Fire Mode Motor Direction
When fire mode is enabled, motor direction will base on the setting of 08-59.
08 – 60: Fire Mode Password
When fire mode is enabled, use can set password in parameter 08-60, please refer the
process of parameter 13-07.
In order to prevent the parameters of fire mode being modified, keypad display will just show
the related parameters of fire mode when fire mode is enabled. (Parameter 08-48~08-60 will
be read only).
Parameter 08-60(password of fire mode) and 13-07(parameter password), only one
parameter can be allowed to set at the same time.
08 - 53
PID Detection Level of Fire Mode
Range
【0~100】%
08 - 54
Delay Time of Fire Mode PID Loss
Range
【0.0~10.0】Sec
08 - 55
PID Feedback Loss Detection Selection of Fire Mode
Range
【0】:Keep Running
【1】:Fire Mode Speed(08-52)
【2】:Max. Output Frequency of Motor 1 (01-02)
When 08-51=1, PID feedback loss detection function will be opened automatically.
When fire mode is enabled, if 08-51=1 and then PID feedback, inverter will be stopped after
the setting value of 08-54.
08 - 55 PID Feedback Loss Detection Selection of Fire Mode
When 08-55=0, output frequency will be fixed on current frequency.
When 08-55=1, output frequency will be based on the setting value of parameter 08-52.
When 08-55=2, output frequency will be based on the setting value of parameter 01-02.
When PID feedback value less than 08-53 and then longer than 08-54, inverter will keep running,
but the frequency reference will be switched to 08-55, output frequency will not less than the
setting value of 08-52.
t
08-54
t1
08-54
FBL
偵測
08-53
回授值
t
PID feedback loss detection
Notes:
If there is no any feedback signal and then feedback loss level also be set to 0%, feedback loss detection
function will not be triggered.
Feedback value
FBL detection