4-200
10-30
Upper Limit of PID Target
Range
0 ~ 100%
10-31
Lower Limit of PID Target
Range 0 ~ 100%
PID target value will be limited to the upper and lower limit range of PID target.
10- 32
PID Switching Function
Range
0:
PID1
1:
PID2
2: Set by DI
3: Set by RTC
10-32=0: PID 1 function is enabled.
PID target value is set by 10-02 and proportional gain, integral time and differential time are set by 10-05,
10-06 and 10-07.
10-32=1: PID 2 function is enabled.
PID target value is set by 10-02 and proportional gain, integral time and differential time are set by 10-36,
10-37 and 10-38.
10-32=2: Set by Digital Input
If the digital input terminal is enabled (digital multi-function terminal is set to 54), PID1 will switch to PID2.
10-32=3: Set by RTC
When RTC timer is enabled, PID1 will switch to PID2.
10- 33
PID Maximum Feedback Value
Range
1~10000
Function of PID maximum feedback value is the 100% corresponding value of 10-02.
10- 34
PID Decimal Width
Range
0~4
Function of PID decimal width enables the user to set the decimal point.
For example, if it is set to 1, the keypad displays the first decimal place XXX.X. If it is set to 2, the keypad
displays the second decimal place XX.XX.
10- 35
PID Unit (Only display in LCD Keypad)
Range
0~24
PID unit enables the user to select the unit for PID target vaule.
When 10-35=0, parameter of 12-38 will be used by the unit of %.