4-206
Figure 4.4.77 Jump frequency operation
Jump frequency via Analog Input.
Set parameter 04-05 (AI2 function selection)
or 04-10 (AI2 function selection) to 9 (frequency jump setting
4) for controlling the jump frequency via analog input AI2. Refer to Fig. 4.4.38.
Note: When jump frequency overlap the sum of the overlapped jump frequencies will be used as the jump
frequency range. Refer to Fig.4.4.78.
Figure 4.4.78 Jump frequency overlap
11- 13
Automatic Return Time
Range
【
0~120】Sec
If the keypad is not pressed within the time set by 11-13, it will automatically return to the mode screen.
When it is set to 0, function of automatic return key is off. Press the return key to return to the previous
directory.
11- 12
Manual Energy Saving Gain
Range 【0~100】%
11- 18
Manual Energy Saving Frequency
Range
【
0.00~599.00】Hz
Manual energy savings reduces the output voltage for the purpose of saving energy.
To enable manual energy savings set one of the multi-function digital input (03-00 to 03-05) to 20 and
activate the input or use parameter 11-18 to set the manual energy savings activation frequency.
When the output frequency rises above the value set in parameter 11-18 manual energy savings function
is enabled. Setting parameter 11-18 manual energy savings frequency to 0.0 Hz disables the manual