4-225
13- 06
Parameters Locked
Range
0:
Only parameter 13-06 and frequency command parameters in main screen
are writable
1:
Only user parameter is enabled.
2:
All parameters are writable.
When 13-06=0, only parameter 13-06 and frequency command parameter in main screen can be set but
other parameters are read-only.
When 13-06=1, only user parameters (00-41~00-56) are enabled. Please refer to the instruction of
parameters 00-41~00-56.
Note: it is only enabled in LCD keypad.
When 13-06=2, all parameters are writable except for the read-only parameters.
Note:
Main frequency setting is 12-16. The value is equal to frequency setting of speed-stage 0 (05-01) in LCD
keypad.
LED Main Frequency can beset in the main frequency display
13- 07
Parameter Password Function
Range
00000~65534
When the setting value of parameter 13-07 is enabled (13-07 > 0), all the parameters can not be
adjusted except the frequency in main screen so user needs to input the password to adjust it.
Password setting:
First step:
Enter the
function
setting at
1
st
time
or
READ/
ENTER
READ/
ENTER
DSP/
FUN