4
-227
13- 08
Restore Factory Setting
Range
【0】:
No Initialization
【1】:
Reserved
【2】: 2 Wire Initialization (220/440V, 60Hz)
【3】:
3 Wire Initialization (220/440V, 60Hz)
【4】: 2 Wire Initialization (230/415V, 50Hz)
【5】:
3 Wire Initialization (230/415V, 50Hz)
【6】: 2 Wire Initialization (200/380V, 50Hz)
【7】:
3 Wire Initialization (200/380V, 50Hz)
【8】: PLC Initialization
【9】: 2 Wire Initialization (230V/460V, 60Hz)
【10】: 3 Wire Initialization (230V/460V, 60Hz)
【11】: 2 wire Initialization (230V/400V, 60Hz)
【12】:
3 wire Initialization (230V/400V, 60Hz)
【13】:
2 wire Initialization (230V/400V, 50Hz)
【14】: 3 wire Initialization (230V/400V, 50Hz)
【15】: 2 wire Initialization (220V/380V, 50Hz)
【16】: 3 wire Initialization (220V/380V, 50Hz)
【Others】: Reserved
Note: Main frequency setting is 12-16. The value is equal to frequency setting of speed-stage 0 (05-01)
Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down the
modified parameters before initializing the inverter. After initialization, the value of 13-08 will return to zero
automatically.
13-08=2: 2-wire initialization (220V/440V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Fig.4.4.1.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class).
When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 60Hz.
13-08=3: 3-wire initialization (220V/440V)
Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are
set for 3-wire start operation and stop command.Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type
operation mode.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class).
When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 60Hz.
13-08=4: 2-wire initialization (230V/415V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Fig.4.4.1.
Inverter input voltage (01-14) is automatically set to 230V (200V class) or 415V (400V class).
When 01-00 (V/F curve) set to F, Inverter maximum frequency (01-12) is automatically set to 50Hz.
13-08=5: 3-wire initialization (230V/415V)