Group 16: LCD Function Parameters
16- 00
Main Screen Monitoring
Range 5~82
16- 01
Sub-Screen Monitoring 1
Range
5~82
16- 02
Sub-Screen Monitoring 2
Range
5~82
At power-up the inverter shows two monitor section on the display, main monitor section and the
sub-screen monitor section (smaller font).
Choose the monitor signal to be displayed as the main-screen monitor screen in parameter 16-00, and the
monitor signals to be displayed on the sub-screen monitor in parameters 16-01 and 16-02, similar to
monitor parameters 12-5 ~ 12-82.
Note: The setting value of 16-00, 16-01 and 16-02 can be modified. It also can reset except PID modes
(refer to the setting description of parameter 10-03) and PUMP modes (refer to the setting
description of parameter 23-00), but these two modes can be modified in inverter software V1.4.
16- 03
Selection of Display Unit
Range
0: Display unit is Hz (Resolution is 0.01Hz)
1: Display unit is % (Resolution is 0.01%)
2: Rpm display; motor rotation speed is set by the control modes to select IM
(02-07)/ PM (22-03) motor poles to calculate.
3~39: Reserved
40~9999: 100% is XXXX with no decimals (integer only)
10001~19999: 100% is XXX.X with 1 decimal
20001~29999: 100% is XX.XX with 2 decimals
30001~39999: 100% is X.XXX with 3 decimals
16- 04
Selection of Engineering Unit
Range
0: No Unit
1: FPM
2: CFM
3: PSI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM *1
22: Bar *1