EasyManua.ls Logo

TECO F510 series - Group 21 Torque Control Parameters

TECO F510 series
555 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-258
Derating of torque compensation function can reduce derating effect of ASR at shock load. Refer to Fig.
4.4.97 & Fig. 4.4.98.
20-34 Derating of Compensation Gain:
This gain effect is the same as the proportional gain of ASR (20-00, 20-02), but it is required to be with the
derating compensation time (20-35) of larger speed tolerance to prevent the inverter from oscillation.
20-35 Derating of Compensation Time:
This time constant is used for the inhibition of oscillation caused from parameter 20-34, but excessive
compensation time constant leading to slower output response is unfavorable to derating compensation.
The recommended setting value of 20-34 is 30~50 and that of 20-35 is 50~100ms.
Group 21 Torque Control Parameters
21- 05
Positive Torque Limit
Range 0~160%
21- 06
Negative Torque Limit
Range
0~160%
21- 07
Forward Regenerative Torque Limit
Range
0~160%
21- 08
Reversal Regenerative Torque Limit
Range
0~160%
Torque limit can be set in two ways:
- Use torque limit parameters (21-05 to 21-08) to set a fixed torque limit.
- Set the torque limit by using the multi-function analog input (AI2).
There are four torque limits that can be set separately, one for each quadrant:
(I) Positive torque limit in forward direction (21-05 positive torque limit)
(II) Positive torque limit of reverse direction (21-08 negative torque limit)
(III) Negative torque limit in reverse direction (21-06 forward regenerating torque limit)
(IV) Negative torque limit in forward direction (21-07 reversal regenerating torque limit)
Refer to Fig.4.4.101.
Figure 4.4.101 Torque limit setting
Torque limit setting by using multi-function analog input AI2 (04-05)

Table of Contents

Other manuals for TECO F510 series

Related product manuals