4-268
23- 05
Display Mode Selection
Range
0: Display of Target and Preesure Feedback
1: Only Display Target Pressure
2: Only Display Pressure Feedback
This function can have the common display of target and feedback pressure or display separately.
when 23-05=0000Led keypad displays pressure setting value and pressure feedback value.
Two-digit in the left is the pressure value setting and two-digit in the right is the pressure feedback value
in the seven-segment monitor.
Note: When 23-00=2 (HVAC), the unit will be multiplied by 1000 times. If the display value is 5.0, it
means 5000GPM (It is only displayed in inverter software V1.4.)
when 23-05=0001Led keypad only displays the pressure setting value.
when 23-05=0002Led keypad only displays the pressure feedback value.
Notes:
- Once the target value is bigger than 10, the target value is only shown as "an integer" instead of "a
decimal." 10-33 is lower than 1000 and 10-34=1 in the PID modes.
- If Pump mode is used in inverter software V1.3, parameter 23-03 is required to set to <= 9.9 PSI.
23- 06
Proportion Gain (P)
Range
0.00~10.00
23- 07
Integral Time (I)
Range
0.0~100.0Sec
23- 08
Differential Time (D)
Range
0.00~10.00Sec