4-271
Note: The purpose of stop time of constant pressure is energy saving.
23- 12
Maximum Pressure Limit
Range
0.10 ~ 650.00PSI *1
0~100% *2
*1: 23-20=0, presents the unit and range.
*2: 23-20=1, presents the unit and range.
It is convenient for user to limit maximum pressure. When pressure feedback value is higher than
maximum pressure limit, the inverter displays warning signal and then stops.
23- 15
Minimum Pressure Limit
Range
0.00 ~650.00PSI *1
0~100% *2
*1: 23-20=0, presents the unit and range.
*2: 23-20=1, presents the unit and range.
It is convenient for user to limit minimum pressure. When pressure feedback value is lower than minimum
pressure limit, the inverter displays warning signal and then stops.
Figure 4.4.106 Diagram for pressure feedback limit
Note: The pressure under the control of PID is between the maximum pressure limit (23-12) and
minimum pressure limit (23-15).
23- 13
Warning Time of High Pressure
Range
0.0 ~ 600.0Sec
When pressure feedback value is higher than maximum pressure limit, warning time of high pressure
starts to count. If pressure feedback value is lower than maximum pressure limit during counting time, the
warning time will recount and the inverter will display the warning signal of HIPb when the warning time
ends.
23- 14
Stop Time of High Pressure
Range
0.0 ~ 600.0Sec
When the warning signal of high pressure occurs and pressure feedback value is higher than maximum
pressure limit, stop time of high pressure starts to count. If pressure feedback value is lower than
maximum pressure limit during counting time, the stop time will recount and the inverter will display stop
error signal of OPbFt when the stop time ends.
23-02 Target Pressure Value
23-12 Maximum Pressure Limit
23-15 Minimum Pressure Limit
Pressure Feedback
Signal