4-274
23- 18
Time of Loss Pressure Detection
Range
0.0 ~ 600.0Sec
23- 19
Proportion of Loss Pressure Detection
Range
0 ~ 100.0%
23- 78
Selection of Loss Pressure Detection
Range
0Disable
1Loss Pressure Warning
2Low Pressure Error
When 23-19 = 0 or 23-78 = 0, function of l
oss pressure detection is disabled.
When 23-19 > 0, If the feedback pressure value is lower than the value of (23-02) x (23-19)and the
detection time of loss pressure (23-18) passes, the inverter jumps to fault signal (FBLSS).
When 23-78=1, the inverter will display warning signal when detecting the loss pressure.
When 23-78=2, the inverter will display error signal when detecting the loss pressure.
23-23 Direction of Water Pressure Detection
Range
0: Upward Detection
1: Downward Detection
23- 24 Range of Water Preesure Detection
Range
0.0 ~ 65.00PSI *1
0~10% *2
23- 25
Period of Water Preesure Detection
Range
0.0 ~ 200.0Sec
23- 26
Acceleration Time of Water Pressure Detection
Range
0.1 ~ 600.0Sec
23- 27
Deceleration Time of Water Pressure Detection
Range
0.1 ~ 600.0Sec
*1: 23-20=0, presents the unit and range.
*2: 23-20=1, presents the unit and range.
Acceleration time of water pressure detection (23-26) and deceleration time of water pressure detection
(23-27) are corresponding to the acceleration time 2 (00-16) and the deceleration time 2 (00-17), so the
setting of 23-26 changed with the setting of 00-16. Thus, avoid using multi-speed application function while
using PUMP function.