4-280
Notes:
- When 23-35=3, If the operation time is over the switching time (23-29) or sleep to stop under the
operation of dual pumps, the dominance between Master and Slave
will exchange to operate.
- When 23-01≠0, the parameter 23-01 of these two inverters can not be simultaneously set to 1 or 2.
That is, the parameter 23-01 of one inverter is set to 1 and that of the other inverter should be set to 2
and vice versa.
Bar
Hz
time
time
Hz
time
Master
Slave
Pressure
Feedback Signal
23-02
Operation
Pressure Setting
23-09
Tolerance Range of
Constant Pressure
Output
Frequency
Output
Frequency
A
BCD
60Hz
E
F
23-30
Detection
Time
23-30
Detection
Time
60Hz
23-10
Sleep Frequency
of Constant
Pressure
23-22
Slave Trip
Frequency
Diagram of sleep stop alternative selection action
Note:
A:Dual pumps are enabled during this time. Higher operation pressure occurs, Master keeps operation
and Slave output frequency decreases.
B:Master operation frequency maintains 60Hz. If water pressure doesn’t decrease to the target constant
pressure and Slave continuously decreases to the set trip frequency (23-22), Slave detection time
(23-30) starts and Slave decelerates to stop.
C:If milder water consumption and higher water pressure occur and Slave operation command is in sleep