3-24
3.3.3.2 General Wiring Diagram (For Enhanced E & G type)
The following is the standard wiring diagram for the F510 inverter (◎ indicates main circuit
terminals and ○ indicates control circuit terminals). Locations and symbols of the wiring terminal
block might be different due to different models of F510. The description of control circuit terminals
and main circuit terminals can be referred to Table 3.3.5.1, 3.3.6.1 and 3.3.6.2
Remarks:
*1: Models IP20 200V 1~30HP, 400V 1~40HP have a built-in braking transistor so that the braking resistor can be
connected between terminal B1 and B2.
*2: The multi-function digital input terminals S1~S6 can be set to Source (PNP) or Sink (NPN) mode via SW6.
*3: Use SW3/SW4 to switch between voltage (0~10V) and current (4~20mA) input for Multi-function analog input 2
(AI2). Besides please also check parameter 04-00 for proper setting.
*4: Run permissive input SF1 & SF2 is a normally closed input. This input should be closed to enable the inverter
output. To activate this input, open the link between SF1/ SF2 and SG.
*5: When using the open collector for pulse input, it doesn’t need resistance because of built-in pull-up resistance.
*6: AO1 / AO2 default setting is 0~+10V.
*7: It need turn on the switch for the terminal resistor RS485 in the last inverter when many inverters in parallel
connection.