4-282
23- 22
Slave Trip Frequency
Range
【0.00~599.00】Hz
If Master and Slave start to run at the same time, Slave will stop depend on the condition listed as below.
When 23-22=0 Hz, if output frequency of Slave is lower than 23-10 (Sleep Frequency of Constant
Pressure) and after the time of 23-11 (Sleep Time of Constant Pressure), the Slave will be stop
automatically.
When 23-22 = 1 ~ 400 Hz (The maximum frequency follow 01-02), if the output frequency of Slave is lower
than 23-22, Master will inform Slave to stop and enter sleep mode, or output frequency of Slave is lower
than 23-10 (Sleep Frequency of Constant Pressure) and after the time of 23-11 (Sleep Time of Constant
Pressure), the Slave will be stop automatically.
23-37
Leakage Detection Time *3
Range
【0.0~100.0】Sec
23-38
Pressure Variation of Leakage Detection Restart *3
Range
【0.01~65.00】PSI *1
【1~10】% *2
23-39
Pressure Tolerance Range of Leakage Detection Restart *3
Range
【0.01~650.00】PSI *1
【1~100】% *2
*1: 23-20=0, presents the unit and range.
*2: 23-20=1, presents the unit and range.
*3: It is new added in inverter software V1.4.
Bar
Hz
time
23-02
Operation Pressure
Setting
time
Pressure Feedback
Value
Output
Frequency
23-37
Leakage
Detection
Time
23-37
Leakage
Detection
Time
∆P1
∆P2
Sleep Leakage Detection Restart
Leakage Detection Case1: Pressure Variation > 23-38
Pressure Variation of Leakage Detection Restart
∆P1 < 23-38
∆P2 > 23-38