EasyManua.ls Logo

TECO F510 series - Page 39

TECO F510 series
555 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-26
PUMP Wiring Diagram for Pressure Sensor of Current Type
Single Pump:
F510 Single Pump Operation
Operation Switch
Pressure
Converter
TM2
SW2
SW3
NPN
J
P
1
J
P
2
V
I
S(+)
S(-)
S1
S3 S5
AI2
E24VGS2S4S6F1F2POP I
24V
+10V
MT
GND GND
AI1
AO2 E
R1A R1B R1C R2A R2C R3A R3C
AO1
00-02=1 (Control Circuit Terminal)
04-00=1 (4mA~20mA); 10-00=0 (Target Source: Keypad)
10-01=2 (Feedback Source: AI2)
10-03=XXX1b (PID is enabled)
23-00=1(Pump); 23-01=0 (Single Pump)
Multi-Pump:
F510 Multi-Pump Operation: Master F510 Multi-Pump Operation: Follower 1
F510 Multi-Pump Operation: Follower 2 F510 Multi-Pump Operation: Follower 3
Operation
Switch
Pressur e
Converter
CON2
TM2
CON2
CON2
CON2
TM2
AB AB
AB AB
S(+) S(-) S1 S3 S5 AI2
E24VGS2S4S6F1F2POP I
24V +10V MT GND GND AI1
AO2 E
R1A R1B R1C R2A R2C R3A R3C
AO1
S(+) S(-) S1 S3 S5 AI2
E24VGS2S4S6F1F2POP I
24V +10V MT GND GND AI1
AO2 E
R1A R1B R1C R2A R2C R3A R3C
AO1
S(+) S(-) S1 S3 S5 AI2
E24VGS2S4S6F1F2POP I
24V +10V MT GND GND AI1
AO2 E
R1A R1B R1C R2A R2C R3A R3C
AO1
TM2
TM2
S(+) S(-) S1 S3 S5 AI2
E24VGS2S4S6F1F2POP I
24V +10V MT GND GND AI1
AO2 E
R1A R1B R1C R2A R2C R3A R3C
AO1
00-02=1 (Control Circuit Terminal); 04-00=1 (4~20mA)
10-00=0 (Target Source: Keypad); 10-01=2 (Feedback Source: AI2
10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=1 (Master)
00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V)
10-00=0 (Target Source: Keypad); 10-01=2 (Feedback Source: AI2
10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=2 (Follower 1)
00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V)
10-00=0 (Target Source: Keypad); 10-01=2 (Feedback Source: AI2
10-03=XXX1b (PID is enabled); 23-00=1(Pump); 23-01=3 (Follower 2)
00-02=1 (Control Circuit Terminal); 04-00=0 (0~10V)
10-00=0 (Target Source: Keypad); 10-01=2 (Feedback Source: AI2
10-03=XXX1b (PID is enabled); 23-00=1(Pump);
23-01=4 (Follower 3)
SW2
SW3
NPN
J
P
1
J
P
2
V
I
Notes: 1. The position of dip switch requires being correct (SW2, SW3).
2. It is required to reconnect after setting Master/ Slave.
3. 24VG and GND require short circuit.

Table of Contents