4-348
No. Object Name Description Unit Classification Range
AO25 StoppingSel
Stop modes
selection
No Units R/W 0 - 1
AO26 FrequenceComm
Main frequency
command source
selection
No Units R/W 0 - 5
AO27 FreqUpperLim Upper limit frequency HZ R/W 0 - 400
AO28 FreqLowerLim
Lower limit
frequency
HZ R/W 0 - 400
AO29 Acc Time1
Acceleration time 1
seconds R/W 0 - 3600
AO30 Dec Time1 Deceleration time 1 seconds R/W 0 - 3600
Table 4.7.4.4 Analog value property list (READ/ WRITE)
No. Object Name Description Unit Classification Range
AV0 PID – P Gain Proportional gain (P) No Units R/W 0 - 10
AV1 PID – I Time Integral time (I) No Units R/W 0 - 100
AV2 PID – D Time Differential time (D) No Units R/W 0 – 10
Table 4.7.4.5 Digital input property list (READ)
No. Object Name Description Unit Classification Range
BI0 Run/Stop Operation status
Stop /
Run
R 0 - 1
BI1 Direction Operation direction FWD/REV R 0 - 1
BI2 ststus Inverter status OK/Fault R 0 - 1
BI3 Abnormal Error occurs
Close/
Open
R 0 - 1
BI4 DI_1 status S1 status
Close/
Open
R 0 - 1
BI5 DI_2 status S2 status
Close/
Open
R 0 - 1
BI6 DI_3 status S3 status
Close/
Open
R 0 - 1
BI7 DI_4 status S4 status
Close/
Open
R 0 - 1
BI8 DI_5 status S5 status
Close/
Open
R 0 - 1
BI9 DI_6 status S6 status
Close/
Open
R 0 - 1
Table 4.7.4.6 Digital output property list (READ/ WRITE)
No. Object Name Description Unit Classification Range
BO0 RY1 status Relay output 1
status
Close/Open R 0 - 1
BO1 RY2 status Relay output 2
status
Close/Open R 0 - 1
BO2 RY3 status Relay output 3
status
Close/Open R 0 - 1
Table 4.7.4.7 Digital value property list (READ/ WRITE)
No. Object Name Description Unit Classification Range
BV0 RUN/STOP RUN/STOP
Stop /
Run
R/W 0 - 1
BV1 FWD/REV FWD/REV FWD/REV R/W 0 - 1