4-352
The followings are parameters F510 models can read and write via MetaSys communication.
Analog input property list (READ)
No. Object Name F510 Parameters Unit Classification Range
AI1 Motor R-RPM
02-03 Motor Rated
Rotation Speed
No Units R 0 ~ 60000
AI2 Motor R-Volt
02-04 Motor Rated
Voltage
Volt R 0~240.0/0~480.0
AI3 Motor R-HP
02-05 Motor Rated Power
horsepower R 0~600.00
AI4 Motor R-Hz
02-06 Motor Rated
Frequency
HZ R 0.00 ~ 400.00
AI5 Comm Station
09-00 INV Communication
Station Address
No Units R 1 - 254
AI6 CommSel
09-01 Communication
Mode Selection
No Units R 0 ~ 3
AI7 BaudRate
09-02 Baud Rate Setting
No Units R 0 ~ 5
AI8 CarrierFreq 11-01 Carrier Frequency KiloHertz R 0 ~ 16
AI9 Freq cmd
12-16 Frequency
Command
HZ R 0.00 ~ 400.00
AI10 Frequency 12-17 Output Frequency HZ R 0.00 ~ 400.00
AI11 Current 12-18 Output Current Amps R 0.0~6553.5
AI12 Control Mode 12-24 Control Mode No Units R 0 ~ 5
AI13 TM2 AIN 12-25 AI1 Input Volt R 0 ~ 100.0
AI14 TM2 AIN2 12-26 AI2 Input Volt R 0 ~ 100.0
AI15 Error code
12-45 Recent Fault
Message
No Units R 0 ~ 45
Analog output property list (READ/ Write)
No. Object Name F510 Parameters Unit Classification Range
AO1 Set frequency Register 2502H HZ R/W 0 ~ 400.00
AO2 AO1 Register 2505H
Volt/
Amps
R 0.00 ~ 100.00
AO3 AO2 Register 2506H
Volt/
Amps
R 0 .00 ~ 100.00
AO4 RunSource
00-02 Main Run Command
Source Selection
No Units R/W 0 ~ 4
AO5 FrequenceComm
00-05 Main Frequency
Command Source
Selection
No Units R/W 0 ~ 6
AO6 FreqUpperLim
00-12 Upper Limit
Frequency
HZ R/W 0 – 109
AO7 FreqLowerLim
00-13 Lower Limit
Frequency
HZ R/W 0 - 109
AO8 Acc Time1
00-14 Acceleration Time 1
seconds R/W 0 ~ 6000.0
AO9 Dec Time1 00-15 Deceleration Time 1 seconds R/W 0 ~ 6000.0
AO10 Motor R-Amp
02-01 Motor Rated Current
Amps R/W 1 ~ 999.9
AO11 FreqCommand1
05-01 Frequency Setting of
Speed-Stage 0
HZ R/W 0 ~ 400.00
AO12 FreqCommand2
06-01 Frequency Setting of
Speed-Stage 1
HZ R/W 0 ~ 400.00
AO13 FreqCommand3
06-02 Frequency Setting of
Speed-Stage 2
HZ R/W 0 ~ 400.00