4-354
Binary input property list (READ)
No. Object Name
No Action /
Action
Classification Range
BI1 Run/ Stop Stop/ Run R 0 - 1
BI2 Direction
Forward/
Reverse
R 0 - 1
BI3 Status OK/ Fault R 0 - 1
BI4 Abnormal Off/ On R 0 - 1
BI5 DI_1 Status Off/ On
R 0 - 1
BI6 DI_2 Status Off/ On
R 0 - 1
BI7 DI_3 Status Off/ On
R 0 - 1
BI8 DI_4 Status Off/ On
R 0 - 1
BI9 DI_5 Status Off/ On
R 0 - 1
BI10 DI_6 Status Off/ On
R 0 - 1
Binary output property list (READ/ WRITE)
No. Object Name
No Action /
Action
Classification Range
BO1 Run/ Stop Stop/ Run R/W 0 - 1
BO2
Forward/
Reverse
Forward/
Reverse
R/W 0 - 1
BO3 RY1 Status Off/ On
R 0 - 1
BO4 RY2 Status Off/ On
R 0 - 1
BO5 RY3 Status Off/ On
R 0 - 1
MetaSys N2 Error Code List
Error Code Cause
00
Without receving Identify command at
power up
01 Receive the non-support command
02 Check Code occurs error
03 Receive the data of more than 256 bits
05 Incorrect command length
10 Data is out of the range
11
Save the undefined fields or the fields that
JCI dedicated
12
The parameter position is only for read
command.