10-3
LED display Description Cause
Possible solutions
OL2
Inverter
overload
Inverter thermal overload
protection tripped.
If an inverter overload
occurs 4 times in five
minutes, it is required to
wait 4 minutes before
resetting the fault.
Voltage setting V/F mode too high,
resulting
in over-excitation of the motor.
Inverter rating too small.
Load too heavy.
Check V/f curve.
Replace inverter with larger
rating.
Check and reduce motor
load, check and operation
duty cycle.
OT
Over torque
detection
Inverter output torque is
higher than 08-15 (over
torque detection level) for
the time specified in 08-16.
Parameter 08-14 = 0 or 2
to activate.
Load too heavy.
Check over torque detection
parameters (08-15 / 08-16).
Check and reduce motor
load, check and operation
duty cycle.
UT
Under torque
detection
Inverter output torque is
lower than 08-19 (under
torque detection level) for
the time specified in 08-20.
Parameter 08-18 = 0 or 2
to activate.
Sudden drop in load.
Belt break.
Check under torque detection
parameters (08-19 / 08-20).
Check load / application.
CE
communication
error
No Modbus communication
received in for the time
specified in 09-06
(communication error
detection time).
Active when 09-07(= 0 to
2).
Connection lost or wire broken.
Host stopped communicating.
Check connection
Check host computer /
software.
FB
PID feedback
loss
PID feedback signal falls
below level specified in
10-12 (PID feedback loss
detection level) for the time
specified in 10-13
(Feedback loss detection
time). Active when
parameter (10-11 = 2).
Feedback signal wire broken
Feedback sensor broken.
Check feedback wiring
Replace feedback sensor.
STO
Safety switch
Inverter safety switches
open.
Terminal board Input F1 and F2 are
not connected (For standard H & C
type)
Terminal board Input SF1 / SF2 and
SG are not connected (For
enhanced E & G type)
08-30 set to 1,free run to stop, and
digital terminal is open, when
03-00~03-07=58
Check F1 and F2 connection.
(For standard H & C type)
Check SF1 / SF2 and SG
connection (For enhanced E
& G type)
Check if 08-30 =0 and
03-00~03-07=58
STO2
Safety switch
SS1
Safety switch
Inverter safety switches
open.
When 08-30 is set to 0:
Deceleration to stop,
and digital
terminal switch(58) is turned on.
Check digital terminal(58) is
turned on.
EF0
External fault 0
External fault (Modbus)
Modbus communication 0x2501 bit 2=
"1"
Reset Modbus
communication 0x2501 bit
2= "1"