10-14
LED display Description
Cause Possible solutions
Operator
Writing Error
Operator cannot write the
information into the inverter.
Data control mode in
operator is not consistent
with that in the inverter.
Data models in operator
are not consistent with that
in the inverter.
Data firmware version in
operator is not consistent
with that in the inverter.
Check the inverters
firmware version/ control
mode/ models
WRE*
Operator
Verifying Error
After operator reads or writes
data in the inverter, user can
verify it. If the data are not
consistent, the inverter
displays the signal of verifying
error.
The data in the operator
and the inverter is not
consistent.
Check if the inverter is
normally connected to
the operator.
VRYE*
Repeat Run
Command
The inverter is only allowed
unidirectional operation and
cannot operate in reverse
direction simultaneously.
Check if the external
terminal is given a run
command in reverse
direction.
Cancel the run command
in reverse direction from
the external terminal.
Operator Read
Prohibit
Selection of allowing reading
(16-08) is set to 0 (Do not
allow to read inverter
parameters and save it to the
operator).
Set parameter 16-08 to 0.
Set parameter 16-08 to 1
(Allow to read inverter
parameters and save it to
the operator).
RDP*
External
Emergency
Stop
Function of external
emergency stop starts.
Parameter 03-00~03-08 is
set to 14 (Function of
emergency stop is
enabled.)
Remove & shutdown the
run command of external
emergency stop and
reset it to multi-function
digital input.
Zero Speed
Stop Warning
The operation signal is
enabled but frequency
command is lower than the
minimum output frequency
(01-08) and DC brake is
disabled.
The frequency command
is not set up.
Set up the frequency
command.
Overload of Air
Compressor
If the inverters output current
reaches OL4 current level
(23-69), OL4 Delay Time
(23-70) passed. When the
count is reached, the inverter
will automatically decelerate
to stop and displays a warning
signal.
Since the current level (23-
69) is set to be over low,
the inverter’s output
current is higher than the
standard one or
compressors current is
used to be over high.
Check if the compressor
load used is higher than
the standard one.
PID feedback
signal loss
When 23-19 > 0, the inverter
will according to feedback
pressure is less than
(pressure transmitter
maximum pressure (23-03) x
proportion of loss pressure
detection (23-19)) value, if the
pressure loss detection time
(23-18) passed and 23-78 = 1
(loss of pressure detection
function) will jump warning
si
g
nal
23-19 proportion of loss
pressure detection is too
big
Feedback sensor install
failure or not work normal.
Check 23-19 setting.
Make sure correct
installation and PID
feedback signal.
* RDEWREVRYERDP warning signals are only displayed in LCD keypad.