11-10
Model
Horse
power
KVA
100% of rated output
current
Rated input
current
Fuse rating
F510-4425-3
425
446 585
643
1000
F510-4535-3
535
526 700
750 1400
F510-4670-3
670
640 875
913 1800
F510-4800-3
800
732 960
1044 2200
IP55 400V class
Model
Horse
power
KVA
100% of rated
output current
Rated input
current
Fuse rating
F510-4001-C3(F)N4 1
2.6 3.4
3.7 10
F510-4002-C3(F)N4 2
3.1 4.1
4.5 16
F510-4003-C3(F)N4 3
4.1 5.4
5.9 16
F510-4005-C3(F)N4 5
7.0 9.2
9.6 20
F510-4008-C3(F)N4 7.5
8.5 12.1
11.6 20
F510-4010-C3(F)N4 10
13.3 17.5
18.2 30
F510-4015-C3(F)N4 15
18 23
24 40
F510-4020-C3(F)N4 20
24 31
34 50
F510-4025-C3(F)N4 25
29 38
41 70
F510-4030-C3(F)N4 30
34 44
48 80
F510-4040-C3(F)N4 40
41 54
59 100
F510-4050-C3(F)N4 50
55 72
68 125
F510-4060-C3(F)N4 60
67 88
96 150
F510-4075-C3N4 75
79 103
112 200
F510-4100-C3N4 100
111 145
140 250
Fuse type: Choose semiconductor fuse to comply with UL.