11-49
Type Terminal Terminal functions Signal level
Relay
Output
R4A-
R4B-
R4C
Relay A contact (multi-function output terminal)
Relay B contact (multi-function output terminal)
Relay shared terminal; please refer to the
manual for its functions.
Terminal capacity:
At 250Vac, 10 mA~1A
At 30Vdc, 10 mA~1A
Digital
Output
DO2
Multi-function (open collector transistor) output:
Operating, zero speed, frequency consistent, any
frequency consistent, output frequency,
preparation complete, low-voltage detection,
output occlusion, operation and frequency
commands, over-torque detection, abnormal,
low-voltage, overheat, motor over-load, frequency
converter over-load output, retrying, signal
abnormal, chronograph output…
48Vdc, 2 mA~50mA
Optical coupling output
DOG
Open collector transistor shared terminal