A-3
Appendix-A Instructions for UL
Recommended Input Fuse Selection
Fuse Type
Drive Model F510 Manufacturer: Bussmann / FERRAZ SHAWMUT
Model
Fuse Ampere Rating (A)
200 V Class Three-Phase Drives
2001 Bussmann 20CT
690V 20A
2002 Bussmann 20CT
690V 20A
2003 Bussmann 30FE
690V 30A
2005 Bussmann 50FE
690V 50A
2008 Bussmann 50FE
690V 50A
2010 Bussmann 63FE
690V 63A
2015 FERRAZ SHAWMUT A50QS100-4
500V 100A
2020
Bussmann 120FEE / FERRAZ A50QS150-4
690V 120A / 500V 150A
2025 FERRAZ SHAWMUT A50QS150-4
500V 150A
2030 FERRAZ SHAWMUT A50QS200-4
500V 200A
2040 FERRAZ SHAWMUT A50QS250-4
500V 250A
2050 FERRAZ SHAWMUT A50QS300-4
500V 300A
2060 FERRAZ SHAWMUT A50QS400-4
500V 400A
2075 FERRAZ SHAWMUT A50QS500-4
500V 500A
2100 FERRAZ SHAWMUT A50QS600-4
500V 600A
2125 FERRAZ SHAWMUT A50QS700-4
500V 700A
Fuse Type
Drive Model F510 Manufacturer: Bussmann / FERRAZ SHAWMUT
Model Fuse Ampere Rating (A)
400 V Class Three-Phase Drives
4001 Bussmann 10CT
690V 10A
4002 Bussmann 10CT
690V 10A
4003 Bussmann 16CT
690V 16A
4005 Bussmann 16CT
690V 16A
4008 Bussmann 25ET
690V 25A
4010 Bussmann 40FE
690V 40A
4015 Bussmann 50FE
690V 50A
4020 Bussmann 63FE
690V 63A
4025 Bussmann 80FE
690V 80A
4030 Bussmann 100FE / FERRAZ A50QS100-4
690V 100A / 500V 100A
4040 Bussmann 120FEE
690V 120A
4050 FERRAZ SHAWMUT A50QS150-4
500V 150A
4060
FERRAZ SHAWMUT A50QS200-4
500V 200A
4075
FERRAZ SHAWMUT A50QS250-4
500V 250A
4100 FERRAZ SHAWMUT A50QS300-4
500V 300A
4125 FERRAZ SHAWMUT A50QS400-4
500V 400A
4150 FERRAZ SHAWMUT A50QS500-4
500V 500A
4175 FERRAZ SHAWMUT A50QS600-4
500V 600A
4215 FERRAZ SHAWMUT A50QS700-4
500V 700A
4250 FERRAZ SHAWMUT A50QS700-4
500V 700A
Motor Overtemperature Protection
Motor overtemperature protection shall be provided in the end use application.
Field Wiring Terminals
All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the proper connections
that are to be made to each terminal and indicate that copper conductors, rated 75°C are to be used.
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will
not rise above value. Please see electrical ratings for maximum voltage and table below for current.
The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or greater than the short-circuit
tolerance of the power supply being used.
Suitable for use on a circuit capable of delivering not more than ( A ) RMS symmetrical amperes for ( Hp ) Hp in 240 / 480 V class
drives motor overload protection.
Horse Power ( Hp ) Current ( A ) Voltage ( V )
1 - 50 5,000 240 / 480
51 - 200 10,000 240 / 480
201 - 400 18,000 240 / 480
401 - 600 30,000 240 / 480