A-5
Appendix-A Instructions for UL- Additional Data
08-06=0: When the inverter detects a motor overload the inverter output is turned off and the OL1 fault message will flash on the
keypad. Press RESET button on the keypad or activate the reset function through the multi-function inputs to reset the OL1 fault.
08-06=1: When the inverter detects a motor overload the inverter will continue running and the OL1 alarm message will flash on the
keypad until the motor current falls within the normal operating range.
Motor overtemperature protection shall be provided in the end use application.
Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge
Terminal
Crimp Terminal
Tool Insulation Cap
2
mm ,
AW
F510
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Screws
Model No.
Machine No.
Model No.
2175 152 (300)*2 M12 R150-12*2
Nichifu NOP 150H TIC 150
4300 203 (400)*2 M12 R200-12S*2
Nichifu NOH 300K TIC 200
4375 253 (500)*2 M12 R325-12S*2
Nichifu NOH 300K TIC 325
4425 253 (500)*2 M12 R325-12S*2
Nichifu NOH 300K TIC 325
◆Type 1
During installation, all conduit hole plugs shall be removed, and all conduit holes shall be used.
Recommended Input Fuse Selection
Fuse Type
Drive Model F510 Manufacturer: Bussmann / FERRAZ SHAWMUT
Model
Fuse Ampere Rating (A)
200 V Class Three-Phase Drives
2150 Bussmann 170M5464 690V 800A
2175 Bussmann 170M5464
690V 800A
Fuse Type
Drive Model A510
Manufacturer: Bussmann / FERRAZ SHAWMUT
Model
Fuse Ampere Rating (A)
400 V Class Three-Phase Drives
4300 Bussmann 170M5464 690V 800A
4375
Bussmann 170M5464
690V 800A
4425
Bussmann 170M5466
690V 1000A