3-56
*1: Take standard 4-pole induction motor as the base.
*2: F510 model is designed to be used in normal duty (ND), whose overload capability is 120% for 1 min.
*3: If it is greater than default carrier frequency, you need to adjust the load current based on the de-rating
curve.
200V class
Carrier freq.
default setting
Carrier freq.
range
400V class
Carrier freq.
default setting
Carrier freq.
range
1~25HP 2KHz 2~16KHz 1~30HP 4KHz 2~16KHz
30HP 2KHz 2~12KHz 40HP 2KHz 2~16KHz
40~50HP 2KHz 2~12KHz (*4) 50~60HP 4KHz 2~12KHz (*4)
60~125HP 2KHz 2~10KHz (*4) 75~215HP 4KHz 2~10KHz (*4)
- - - 250HP 2KHz 2~8KHz
150~175HP 2KHz 2~5KHz 300~375HP 4KHz 2~5KHz
- - - 425HP 2KHz 2~5KHz
- - - 535~800HP 4KHz 2~5KHz
*4: If control mode is set to SLV mode and maximum frequency (01-02) is larger than 80 Hz, the carrier
frequency range is 2~8Hz.
The following table shows the maximum output frequency for each control mode.
Control
mode
Other settings
Maximum
output
frequency
V/F Unlimited 599Hz
SLV
200V 1~15HP, 400V 1~20HP 150Hz
200V 20~30HP, 400V 25HP 110Hz
400V 30~40HP 100Hz
200V 40~125HP, 400V 50~215HP,
carrier (11-01) is set as 8K or below 8K.
100Hz
200V 40~125HP, 400V 50~215HP,
carrier (11-01) is set as above 8K.
80Hz
200V 150~175HP, 400V 250~800HP 100Hz
PMSLV Unlimited 599Hz