TEKNİM PARS SERIES INTRUDER ALARM SYSTEM INSTALLATION AND PROGRAMMING MANUAL
PGM is active when selected
errors occur.
Door lock open hold time can be entered in the range of 1-255 sec.
The PGM remains on for the specified time and then turns off. Can be
entered between 1-255 sec.
PGM will open and close
randomly according to the
entered value.
When the alarm system is armed, PGM remains open for the entered
parameter value. Parameter can be entered between 0-255min.
When the alarm system is disrmed, the PGM remains on until the entered
parameter value. Parameter can be entered between 0-255min.
PGM activated by remote control. Parameter can be entered between 0-
255min.
PGM is activated
according to the selected
alarm type.
• LED Keypad;
[13] [01] → [0-1-2-…-15] → [√ OK]
• LCD Keypad;
[Panel Settings √ OK]→[PGM Settings √ OK]→[User PGM 1 As {Select Value by (B) (C) Keys}]→[√ OK]
PGM Settings
PGM parameter varies according to the selected PGM type. The table above shows what this
parameter means and the setting options for each PGM type. If more than one option is selected, the
sum of the values corresponding to the options must be entered.
• LED Keypad;
[13] [02] → [XXX] → [√ OK]
• LCD Keypad;
[Panel Settings √ OK]→[PGM Settings √ OK]→[PGM Settings XXX]→[√ OK]
eg. If PGM is selected as Alarm type and is required to be active in Fire alarm and Medical alarm conditions;
The value specified for the fire alarm (4) and the value specified for the medical alarm (32) are added and the
value found (36) is entered. [13] [02] → [36] → [√ OK]