30 Addressable Fire Panel IRIS - Installation and Programming Manual
Fig. Screen 13c - SensoIRIS M140 re detector.
On Fig. Screen 13c is shown the SensoIRIS M140 (addressable optical smoke and temperature RoR detector) settings
screen. Choose the “MORE” button to enter a screen with additional settings:
 - A digit number sent form the devices to the control panel.
 - Button for changing the LED mode: ON Setting - The LED blinks at every query from the station; OFF
Setting - The LED does not show the dialogue cycle.
. Set here the sensitivity level of the optical parts of the detector and enable/ disable the heat part.
These settings are valid for the daytime:
- Sensitivity level. There are 4 levels for setting of alarm level sensitivity for the optical part: High, Normal,
Middle and Low. To change the level of sensitivity simple press the active button next to the eld and choose
a new level from the list.
- Heat part. In addition for this device only the installer can enable or disable the heat part of the detector. The
state of the heat part can be changed with pressing the button.
. Set here the sensitivity level of the optical parts of the detector and enable/ disable the heat part.
These settings are valid for the nighttime. Operation of setting is the same with those for the day alarm level.
Attention: It is not allowed disabling the temperature and the optical parts at the same time!
To save the new setting press the “SAVE” button on the main screen.
Fig. Screen 13d - B24A re base for conventional SensoMAG detectors.
Day Verify Time (seconds) - Setting of daytime conrmation of alarm.
Night Verify Time (seconds) - Setting of nighttime conrmation of alarm.
Important Note: The alarm must remain active during the programmable period of time in order to generate
an alarm event from the panel. If the detector restores its normal state prior to time-out, the panel shall not
generate alarm.