132
6 F 2 S 0 7 1 5
Displaying Symmetrical Component
This part describes how to display the positive phase, the negative phase and the zero phase
components for 1 cycle before the active cursor position.
Note for Operation
Select phase order before operating.
(2.1 Setting Parameters for Measurement and Analysis Selecting Phase Order)
You can select the primary values or the secondary values for the symmetrical
components. You can select the leading display or delay display for the phase
differences.
(2.1 Setting Parameters for Measurement and Analysis Selecting Options)
Operating Procedure
Display the active cursor at the measurement point.
On the [Analysis] menu, click [Symmetrical Component].
The symmetrical components and the phase differences of the current phase order
setting are displayed.
The symmetrical components for 1 cycle before the cursor position are calculated.
You can update the values by moving the cursor.
[--------] is displayed where it can not be analyzed.
2-20