152
6 F 2 S 0 7 1 5
Click the down arrow button that appears just to the right of [Measuring Phase] drop-
down list box and click the measurement phase to display the locus diagram.
Click the down arrow button that appears just to the right of [Step] drop-down list box
and click the calculation interval of the locus.
Type the calculation range of the locus in [Calculate Range] text boxes.
Specify the calculation range from 20.0 ms or later from the beginning of the waveforms.
To calculate the range between Cursor 0 and Cursor 2 (the fault detection point and the restoration from
fault point), clickCursor 0-2button.
To calculate the entire range, clickAllbutton.
To optimize the locus diagram, check [Auto Scale] check box.
The scale is changed automatically and the locus diagram is expanded to the entire screen to be
displayed.
To change the scale of the locus diagram, do not check [Auto Scale] check box.
Then, type the scales values the elements in [Scale] text boxes.
Type the values for 1 scale.
To calculate the fundamental waveform component only, check [Calculate with only
fundamental waveform] check box.
To display the time every time the locus advances for the specific distance, check
[Display Time] check box.
To display the time every specific time, check [Display Time] check box, check
[Interval Time] check box and type the display interval the text boxes.
3-4