E6582175
E-18
5
3) Using other speed commands with preset-speed command
Command mode
selection

0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: CANopen communication
4: Communication option
Frequency setting
mode selection

0:Setting dial 1 (save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sr0
0:Setting dial 1 (save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sr0
Preset-
speed
command
Active Preset-speed command valid Note)
Inactive Command set with fmod is valid
Note) The preset-speed command is always given priority when other speed commands are input at the same time.
An example of three-speed operation with the default settings is shown below.
(Frequency settings are required for  to .)
F-CC
S1(SS1)-CC
S2(SS2)-CC
ON
OFF
ON
OFF
ON
OFF



Output frequency
Time
0
(The inverter doesn't accept
Preset-speed command.)

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)

Related product manuals