E6582175
F-3
6
Note1: The parameters set by communication option or RS485 communication are not searched and not
displayed.
Note2: The following parameters are not displayed in this auh, even if they are the most recent changes.
fc (Operation frequency of operation panel), auf (Guidance function),
aul (Overload characteristic selection), au1 (Automatic acceleration/deceleration),
au2 (Torque boost setting macro function), typ (Default setting),
set (Checking the region setting), f700 (Parameter protection selection) ,
f737 (All key operation prohibition ) , f738 (Password setting (f700)) ,
f739 (Password verification)
6.1.2 Application easy setting (aua)
aua : Application easy setting
[Parameter setting]
Title Function Adjustment range Default setting
aua
Application easy setting
0:-
1: Initial easy setting
2: Conveyor
3: Material handling
4: Hoisting
5: Fan
6: Pump
7:Compressor
0
Application easy setting (aua):
Parameters necessary to your machine can be set easily using the application easy setting.
The parameters necessary to the machine is set to easy setting mode parameters 1-32 (f751-f782). Set the
parameters using the easy setting mode. (Refer to section 4.5.)