E6582175
F-39
6
For details about analog signal setting, refer to section 7.3.
1) 0-10Vdc voltage input adjustment (VIA, VIB terminals)
A
djust the frequency command for
the voltage input by setting the two
points.
/
100 (%)
10V voltage signal
/
0 ( Hz)
/
0 (%)
0
/
50/60 (Hz)
Frequency commnd


2) 4-20mAdc current input adjustment (VIC terminal)
A dju st t he fr eq ue nc y c om m and f or th e
cu rr en t in pu t b y s ettin g the t wo po ints.
Set  to in cas e o f a cu rr e nt
in pu t o f 0 to 2 0 m A.

10 0 ( % )
20mA current signal

0 ( Hz)

2 0 (%)
4mA

50 /60 ( H z)
Frequency commnd
3) -10-+10 Vdc voltage input adjustment (VIB terminal)
A
djust the frequency
command for the voltage
input by setting the two
points.

50/60 (Hz)

100(%)
10V voltage signal
-100(%)
-10V

f213
50/60 (Hz)


Forward run
Reverse run
0(Hz)
0(%)