F-74
6
6.19.6 Output voltage adjustment/Supply voltage correction
vlv : Base frequency voltage 1
f307 : Supply voltage correction (output voltage limitation)
Function
Supply voltage correction: Prevent torque decline during low-speed operation.
Maintains a constant V/F ratio, even when the input voltage fluctuates.
Output voltage limitation: Limits the voltage to prevent outputting the voltage exceeding base frequency
voltage (vlv). Applied when operating a special motor with low induced
voltage.
[Parameter setting]
Title Function Ad
j
ustment ran
g
e Default settin
g
vlv Base frequency voltage1
50-330 (240V class)
50-660 (500V class)
*1
f307
Supply voltage correction
(output voltage limitation)
0: Supply voltage uncorrected,
output voltage limited
*1
1: Supply voltage corrected,
output voltage limited
2: Supply voltage uncorrected,
output voltage unlimited
3: Supply voltage corrected,
output voltage unlimited
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
If f307 is set to "0" or "2" (Supply voltage uncorrected), the output voltage will change in proportion to
the input voltage.
Even if the base frequency voltage (vlv parameter ) is set above the input voltage, the output voltage
will not exceed the input voltage.
When the V/F control mode selection parameter () is set to any number between 2 to 6, the supply
voltage is corrected regardless of the setting of f307.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)