E6582175
F-128
6
Title Function Adjustment range Default setting
f734
Panel emergency stop operation
prohibition
0: Permitted, 1: Prohibited 0
f735
Panel reset operation prohibition 0: Permitted, 1: Prohibited 0
f736
cmod / fmod change prohibition
during operation
0: Permitted, 1: Prohibited 1
All key operation prohibition Note 2) 0: Permitted, 1: Prohibited 0
f738
Password setting (
f700)
0: Password unset
1-9998
9999: Password set
0
f739
Password verification
0: Password unset
1-9998
9999: Password set
0
● Parameters can be edited regardless of the setting of f700 by assigning the parameter editing
permission (function number 110, 111) to an input terminal.
Note1:
f700=2 and 4 will be available after reset operation.
Note 2: Turn off and turn on again after the
f737 setting to take effect the setting.
Note 3: The frequency setting(
fc, fpid, Preset-speed frequency) by the setting dial in the standard
monitor mode cannot be prohibited by
f700.
Set 1
f731= 1 to prohibit the frequency setting.
1) Setup and resetting method when protection using a password is necessary
■ Password setup method
Preparation: Parameters other than f700, f738, and f739 cannot be changed when f700 is set
to
1 to 4.
(1) When
f738 or f739 is read out and the value is 0, a password hasn’t been set.
You can set a password.
(2) When
f738 or f739 is read out and the value is 9999, a password has already been set.
(3) You can set a password If it hasn’t been set. Select and register a number from
1 to 9998 for f738.
The number is the password. Do not forget your password as it is required to release the lock.
(4) The settings for parameter
f700 cannot be changed.
Note 4: The lock cannot be released If you forget the password. Do not forget this password as we cannot
retrieve it.
Note 5: Password cannot be set when parameter
f700=0.
Set the password after parameter
f700=1 to 4.
Note 6: Password can be read out to parameter writer (optional device) only for 5 minutes after setting
. Please note that password will not be able to read out due to password protection after 5
minutes have elapsed or when the power is off.