7.3.3 Settings depending on voltage (-10 to +10 V) input
You can set the frequency settings by inputting an analog voltage signal of -10 to +10Vdc between the VIB and
CC terminals.
The following shows examples when the run command is input from the terminal.
Title Function Adjustment range Default setting Setting example
 Command mode selection
0 – 4
1
(panel keypad)
0
(terminal block)

Frequency setting mode
selection
0 – 14
0
(setting dial 1)
2
(terminal VIB)

Analog input terminal
selection (VIB)
0: 0-+10V
1: -10-+10V
0
1
(-10 - +10V)

Analog/logic input selection
(
VIA/VIB
)
0 – 4
0
0
(Analog input)
 VIB input point 1 settin
g
-100 - +100% 0 0
 VIB input point 1 frequency 0.0 - 500.0Hz 0.0 0.0
 VIB input point 2 settin
g
-100 - +100% 100 100
 VIB input point 2 frequency 0.0 - 500.0Hz
*1 50.0/60.0
 Analo
g
input filter 2 - 1000 ms 64 64
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Motor
M
R/L1
U/T1
MCCB
Powe
r
Supply
S/L2
T/L3
V/T2
W/T3
CC
FLC
VIB
PP
VF-S15
Run and stop settings
You can switch between forward run (F)
and reverser run (R), and run/stop with
external signals.
Setting characteristics for the voltage
input signal and frequency
Set characteristics at two points.
Forward
run
Reverse
r
un
* Connect a single-phase
input model to R/L1 and
S/L2/N.
FLA
FLB
CC
F
R
S1
S2
S3
RES
±
0
-10 to +10 Vdc
%




Point 2
Point 1
Voltage input signal
-100% 0% 100%
(-10V) (0V) (+10V)
Frequency (Hz)
Forward run
Reverse run

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)

Related product manuals