E6582175
17
In case of replacing inverter of software version V116 or earlier
Regarding all of the parameters on Table 1, copy all of the parameter setting values from V116 or earlier version inverter, and then set
them to V120 or later version inverter. Same motor control characteristics will be obtained.
f456 to f458 are manufacturer setting parameters. However, change these parameters according to Table 4 for achieving
same motor control characteristics.
(f456 and f457 do not exist on V110 or earlier version inverter.)
Impact of using traditional IE1 motor with default setting
When traditional IE1 motor is driven by V120 or later version inverter with their default setting values described on Table 3,
following operation can be impacted.
- Torque boost is set to low. Therefore, motor torque can be insufficient at low speed.
Countermeasure: Set the parameter on Table 4.
- Motor rated speed is set to high. Therefore, motor slip can become larger than expected one at vector control.
Countermeasure: Set the parameter values on Table 4, and apply auto tuning.
Search changed parameters
g
gg
gr
rr
ru
uu
u
In case of copying parameters from V116 or earlier version inverter to V120 or later version inverter, the parameters described on
Table 1 are searched on the Searching Changed Parameters (gru: Automatic edit function).
Copying on opposite direction is led to the similar result.
(f456 and f457 do not exist on V110 or earlier version inverter.)
Communication tool
PCM002Z
In case of reading the parameters of V116 or earlier version inverter by the parameter list of V120 or later version (for IE3 motor) in
maintenance communication tool (PCM002Z), PCM002Z displays as ‘modified’ for the parameters described on Table 1.
Reading with the opposite relation of their software version is led to the similar result.
(f456 and f457 do not exist on V110 or earlier version inverter.)
S-2

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)