CDHH-SVX003C-EN
19
General Weights
Weights (lb)
Important: The weight information provided here should be
used for general information only. Trane does
not recommend using this weight information
for considerations relative to chiller handling,
rigging, or placement. The large number of
variances between chiller selections drives
variances in chiller weights that are not
recognized in these tables. For specific
weights for your chiller, refer to your submittal
package.
Table 2. Representative weights, 60 Hz chillers (lb)
Model
Comp Size
CPKW
Evap Size
Cond Size
Weights without Starters
NTON EVSZ CDSZ
Operating Shipping
CDHH
2000–2600 1340 400M 440M 124422 100930
2800–3300 1340 440M 440M 134278 108299
2800–3300 1340 440X 440X 141614 113420
Notes:
1. TECU tubes, 0.028 in. tube wall thickness.
2. 300 psig marine waterboxes.
3. Heaviest possible bundle and motor combination.
4. Operating weights assume the largest possible refrigerant charge.
5. Industrial Control Panel (INDP) option, add 50 lb.
6. Control Power Transformer (CPTR) option, add 280 lb.
7. Supplemental Motor Protection (SMP) option, add 500 lb.
8. To calculate the maximum chiller weight with starter/drive, add the starter/AFD weight from the following table (maximum weights, unit-mounted starters/AFDs [lb]) to
the chiller maximum weight from this table. Note that Duplex™ chiller models CDHH will have two starters, one for each compressor.
Table 3. Representative weights, 50Hz chillers (lb)
Model
Comp Size
CPKW
Evap Size
Cond Size
Weights without Starters
NTON EVSZ CDSZ
Operating Shipping
CDHH
1750–2250 1023 400M 440M 127870 104378
3050 1023 440M 440M 137126 111147
3050 1023 440X 440X 144462 116268
Notes:
1. TECU tubes, 0.028 in. tube wall thickness.
2. 300 psig marine waterboxes.
3. Heaviest possible bundle and motor combination.
4. Operating weights assume the largest possible refrigerant charge.
5. Industrial Control Panel (INDP) option, add 50 lb.
6. Control Power Transformer (CPTR) option, add 280 lb.
7. Supplemental Motor Protection (SMP) option, add 500 lb.
8. To calculate the maximum chiller weight with starter/drive, add the starter/AFD weight from the following table (maximum weights, unit-mounted starters/AFDs [lb]) to
the chiller maximum weight from this table. Note that Duplex™ chiller models CDHH will have two starters, one for each compressor.
Table 4. Maximum weights, unit-mounted starters/Adaptive Frequency™ Drives (AFDs) (lb)
Low Voltage (less than 600 volts) Wye-delta
557
Adaptive Frequency Drive (less than 600 volts)
900 amp
3000
1210 amp
3000
Medium Voltage (2300–6600 volts)
Across-the-line 652
Primary Reactor
1602
Autotransformer 1702
Note: All weights are nominal and ±10%.