EasyManua.ls Logo

Trane CenTraVac CDHH - System Control Circuit Wiring (Field Wiring)

Trane CenTraVac CDHH
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70
CDHH-SVX003C-EN
System Control Circuit Wiring (Field Wiring)
Table 23. Unit control panel wiring 120 Vac
Standard Control Circuits: Unit
Control Panel Control Wiring
(120 Vac)
Unit Control Terminations
Input or Output Type
Contacts
Chilled Water Flow Proving Input
(a)
1X1-5 to 1K16-J3-2 Left Panel
Binary Input Normally Open, Closure with Flow
Condenser Water Flow Proving Input
(b)
1X1-6 to 1K16-J2-2 Left Panel
Binary Input Normally Open, Closure with Flow
Chilled Water Pump Relay Output
1K15-J2-4 to 6 Left Panel
Binary Output Normally Open
Condenser Water Pump Relay Output
1K15-J2-1 to 3 Left Panel
Binary Output Normally Open
Optional Control Circuits (120 Vac) Note: Defaults are factory programmed; alternates can be selected at start-up using the service tool.
Alarm Relay MAR (Non-Latching)
Output
1K19-J2-1 to 3 Left Panel
Binary Output Normally Open
Limit Warning Relay Output
1K19-J2-4 to 6 Left Panel
Binary Output Normally Open
Alarm Relay MMR (Latching) Output
1K19-J2-7 to 9 Left Panel
Binary Output Normally Open
Compressor Running Relay Output
1K19-J2-10 to 12 Left Panel
Binary Output Normally Open
Maximum Capacity Relay Output
1K20-J2-1 to 3 Left Panel
Binary Output Normally Open
Head Relief Request Relay Output
1K20-J2-4 to 6 Left Panel
Binary Output Normally Open
Circuit 2 Purge Alarm Relay Output
1K20-J2-7 to 9 Left Panel
Binary Output Normally Open
Circuit 1 Purge Alarm Relay Output
1K20-J2-10 to 12 Left Panel
Ice Making Relay Output
1K15-J2-10 to 12 Left Panel
Binary Output Normally Open
Alternates
Circuit 1 Running
Circuit 2 Running
Chiller Alarm
Circuit 1 Alarm
Circuit 2 Alarm
Purge Alarm
Standard Low Voltage Circuits (Less
than 30 Vac)
(c)
Unit Control Panel Terminations
Input or Output Type
Contacts
External Auto Stop Input
1K2-J2-1 to 2 Left Panel
Binary Input Closure Required for Normal Operation
Emergency Stop Input
1K2-J2-3 to 4 Left Panel
Binary Input Closure Required for Normal Operation
Circuit 1 External Lockout 12K11-J2-1 to 2 Left Panel
Binary Input Closure Required for Normal Operation
Circuit 2 External Lockout 1K211-J2-3 to 4 Left Panel
Binary Input Closure Required for Normal Operation
Optional Low Voltage Circuits
External Base Loading Enable Input
1K8-J2-1 to 2 Left Panel
Binary Input Normally Open
External Hot Water Control Enable Input
1K8-J2-3 to 4 Left Panel
Binary Input Normally Open
External Ice Building Control Enable
Input
1K9-J2-1 to 2 Left Panel
Binary Input Normally Open
% RLA Compressor Output (Circuit 1
Left Panel 1K5)
1K5-J2-1 to 3 Left Panel
Analog Output
2–10 Vdc
External Condenser Pressure Output
(Circuit 1 Left Panel 1K5)
1K5-J2-4 to 6 Left Panel
Analog Output
2–10 Vdc
Evaporator/Condenser Differential
Pressure Output (Circuit 1 Left Panel
1K5)
1K5-J2-4 to 6 Left Panel
Analog Output
2–10 Vdc
Condenser Head Pressure Control
(Circuit 1 Left Panel 1K5)
1K5-J2-4 to 6 Left Panel
Analog Output
2–10 Vdc
External Demand Limit Setpoint Input
1K6-J2-2 to 3 Left Panel
Analog Input
2–10 Vdc, or 4–20 mA
External Chilled Water Setpoint Input
1K6-J2-5 to 6 Left Panel
Analog Input
2–10 Vdc, or 4–20 mA
External Base Loading Setpoint Input
1K7-J2-2 to 3 Left Panel
Analog Input
2–10 Vdc, or 4–20 mA
Generic Refrigerant Monitor Input
1K7-J2-5 to 6 Left Panel
Analog Input
2–10 Vdc, or 4–20 mA
Outdoor Air Temperature Sensor
Inter-processor Communication (IPC)
Bus Connection and Sensor
Communication and Sensor

Table of Contents

Related product manuals