[80] No Flow
[81] Dry Pump
[82] End of Curve
[83] Broken Belt
13-41 Logic Rule Operator 1
Array [6]
Option: Function:
Select the first logical operator to use on the Boolean inputs from par.
13-40
Logic Rule Boolean 1 and par.13-42 Logic Rule Boolean 2.
[13 -XX] signifies the boolean input of par. 13-*.
[0] * DISABLED Ignores par.13-42
Logic Rule Boolean 2, par.13-43 Logic Rule Operator
2, and par.13-44 Logic Rule Boolean 3.
[1] AND Evaluates the expression [13-40] AND [13-42].
[2] OR evaluates the expression [13-40] OR[13-42].
[3] AND NOT evaluates the expression [13-40] AND NOT [13-42].
[4] OR NOT evaluates the expression [13-40] OR NOT [13-42].
[5] NOT AND evaluates the expression NOT [13-40] AND [13-42].
[6] NOT OR evaluates the expression NOT [13-40] OR [13-42].
[7] NOT AND NOT evaluates the expression NOT [13-40] AND NOT [13-42].
[8] NOT OR NOT evaluates the expression NOT [13-40] OR NOT [13-42].
13-42 Logic Rule Boolean 2
Array [6]
Option: Function:
Select the second boolean (TRUE or FALSE) input for the selected logic
rule.
See par.13-40
Logic Rule Boolean 1 for further descriptions of choices
and their functions.
[0] * False
[1] True
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current limit
[7] Out of current range
[8] Below I low
[9] Above I high
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
Parameter Description
144 TR200 Programming Guide

Table of Contents

Other manuals for Trane TR200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TR200 Series and is the answer not in the manual?

Trane TR200 Series Specifications

General IconGeneral
Input Voltage24 VAC
Frequency Range50/60 Hz
Communication ProtocolsBACnet MS/TP, Modbus RTU
Controller TypeProgrammable
Power Range20 VA
Control MethodPID Control
Enclosure RatingIP20
Operating Temperature32°F to 122°F (0°C to 50°C)
Humidity Range5% to 95% non-condensing
MemoryNon-volatile

Related product manuals