Read-out and Programming of Indexed Parameters
Parameters are indexed when placed in a rolling stack.
par.15-30
Alarm Log: Error Code to par.15-33 Alarm Log: Date and Time contain a fault log which can be read
out. Choose a parameter, press [OK], and use the up/down navigation keys to scroll through the value log.
Use par.3-10
Preset Reference as another example:
Choose the parameter, press [OK], and use the up/down navigation keys keys to scroll through the indexed
values. To change the parameter value, select the indexed value and press [OK]. Change the value by using the
up/down keys. Press [OK] to accept the new setting. Press [CANCEL] to abort. Press [Back] to leave the parameter.
Initialization to Default Settings
Initialize the frequency converter to default settings in two ways:
Recommended initialization (via par.14-22
Operation Mode)
1. Select par.14-22
Operation Mode
2. Press [OK]
3. Select “Initialization”
4. Press [OK]
5. Cut off the mains supply and wait until the dis-
play turns off.
6. Reconnect the mains supply - the frequency con-
verter is now reset.
7.
Change par.14-22
Operation Mode back to
Nor-
mal Operation
.
Note
Resets parameters selected in Personal Menu with default factory setting.
par.14-22 Operation Mode initializes all except:
par.14-50 RFI Filter
par.8-30
Protocol
par.8-31 Address
par.8-32
Baud Rate
par.8-35 Minimum Response Delay
par.8-36
Maximum Response Delay
par.8-37 Maximum Inter-Char Delay
par.15-00
Operating Hours to par.15-05 Over Volt's
par.15-20 Historic Log: Event to par.15-22 Historic Log: Time
par.15-30
Alarm Log: Error Code to par.15-32 Alarm Log: Time
Manual initialization
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to default settings.
This procedure initializes all except: par.15-00 Operating Hours; par.15-03 Power Up's; par.15-04 Over Temp's; par.15-05 Over Volt's.
Note
When you carry out manual initialisation, you also reset serial communication, par.14-50
RFI Filter and fault log
settings.
Removes parameters selected in par.PC-00
Pump Controller.
Note
After initialization and power cycling, the display will not show any information until after a couple of minutes.
How to Program
TR200 Programming Guide 37