UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 20
Revision 7/06.12 of 63
Table 2
Means of control
Condition of the fire
extinguishing
control panel
Access
level
operation
Access level 2 key
Level 1
Status
Level 2
Status
Button Line Reset
Fire condition
Level 2
Output from Fire Condition stage I or Fire
condition stage II initiated on the display
Button
Outputs
Fire condition, phase
Fire condition Stage I
Level 2
- if outcomes for Fire condition Stage I are
activated to suppress them;
- if outcomes for Fire condition Stage I are
suppressed to activate them
Fire condition, phase
Fire condition Stage II
Level 2
- If the common output for fire condition is
activated to suppress it;
- if there is no activated common output for
fire condition to activate it
Button Alarm
Fire condition Stage I
or Stage II and Fault
condition*
Level 1
To suppress/activate the local sounder
Button Menu
Duty Mode, Fire
condition, Fault
condition*, Test and
Disabled component
Levels 1
and 2
To enter Information and Control Mode
Information and
Control Mode
Levels 1
and 2
- To enter the selected menu;
- To execute the selected command;
- To save the modified parameter
Set up Mode
Level
Button Down
Fire condition
Levels 1 and 2
To show on the display the next message for fire condition
Information and
Control Mode
Levels 1
and 2
- To show on the display the next element
from the menu;
- To move the cursor;
- To modify the selected parameter
Set up Mode
Level
Button Up
Fire Condition
Levels 1
and 2
To show on the display the previous
message for fire condition
Information and
Control Mode
Levels 1
and 2
- To show on the display the previous
element from the menu;
- To modify the selected parameter
Set up Mode
Level
Button Cancel
Information and
Control Mode
Levels 1
and 2
- To exit a function without saving changes
in the parameter; the command will not be
executed;
- To exit the current menu and to move to
an upper hierarchy menu
Set up Mode
Level
* Not operating in Fault condition (fatal fault condition except New Configuration).
5.3. Conditions of the Fire Extinguishing Control Panel
The fire extinguishing control panel FS5200Е monitors the fire detecting lines and the monitored
outputs as it scans consecutively their status. Depending on the current the fire extinguishing control
panel could be in Duty Mode, in Fire condition or Fault condition (short circuit or interruption).
Depending on the measured parameters the inputs could be in Fault condition (short circuit or