UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 48
Revision 7/06.12 of 63
13.4.1.4. Function Check Ground
The screen provides the possibility to
indicate if check ground is being performed or
not. Check ground is disabled only if Zener
barriers or other devices that might cause
ground fault are used however that disable
does not have an effect on the functions of
the of the fire extinguishing control panel.
The factory setting of this parameter is Check
Ground ON.
The admissible values are Check
Ground ON or OFF.
1 2 3
Use the buttons (Down) and (Up) to change alternatively the parameter, the
button to confirm the new value and the button to exit.
13.4.2. Menu “CAN Parameters”
Fire extinguishing Control Panel communicates in a network on CAN interface with the devices from
IFS7000 as transmitting and receiving information. It is necessary for the programable sofwear of the
panel to be 13.10 version or higher.
Functionallity:
Connected in network, FS5200E operates with up to 8 Control panels (Remote control
panels) of series 7000.
It is necessary for the local network to operate with at least 1 panel from series 7000;
Only the panel from 7000 series is definedas the main panel;
Information of Fire condition or Fault condition of FS5200E is accepted and indicated only
from panels 7000 series;
Maximum number of devices on CAN network - up to 32 ( i.e maximum laden network can
be built of 8 panels series 7000 and 24 FS5200E panels.
Communication
Communication FS5200E IFS7000”
In Fire condition of FS5200E, 3 types of conditions are transmitted and indicated
of all the panels series 7000:
- FIRE Condition Stage 1;
- FIRE Condition Stage 2 evacuacion;
- FIRE Condition Stage 2 exting.ON
In Fault condition of FS5200E the following conditions are indicated and
transfered into the panels series 7000:
- Fault in Fire detector of Line 1;
- Fault in Fire detector of Line 2;
- Fault in Fire detector of Line 3;
- Fault in Manual Release Mode;
- Fault in Line Mode;
- Fault in Line Disable Extinguishing;
- Fault in Line Low Pressure;
- Fault in Line Hold Extinguishing;
- Fault in Exit Extinguishing;
- Fault Exit Fire Stage 1;
- Fault Exit Fire Stage 2;
- Fault in Back up battery supply;
- Fault in Mains supply
Communication ''5200E IFS7000”