UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 22
Revision 7/06.12 of 63
- An automatic fire detector is activated along the first or the second or the third line
To exit this condition press button at Access level 2
7.2. Indication
7.2.1. LED and sound indication
In this condition:
- The indicator (Power Supply) illuminates in green light;
- The indicator (Fire condition Stage I) illuminates in red light;
- The indicator of the respective line in Fire condition illuminates in red light;
- If the outputs for phase Fire condition Stage I are suppressed by button (Outputs), the
LED indicator of the button illuminates in continuous red light.
- If the sound indication is suppressed by button (Alarm) the LED indicator of the button
illuminates in continues red light.
- The indicator (Manual Mode) or the indicator (Manual-Automatic Mode) illuminates
in yellow light depending on the selected mode of operation.
The local sounder produces discontinuous signal.
7.2.2. Text message
In this condition the display is
divided into two text fields. The top
one shows the condition of the
control panel, the bottom one the
condition of the lines.
Example: Fire condition is
registered along the first line. The
indicator of line 1 and the indicator
for Fire condition Stage I illuminate
in red light. The text message
shows the Fire condition stage and
the line in which the fire
extinguishing control panel is in
Fire condition.
1 2 3
Potential free relays Rele 1St and Rele Fire are activated. Voltage 28V DC is supplied to the sounder
output S1.
7.3. Using the keypad
Button
Access
level
Operation
Additional information
Button
(Alarm)
all
Press it to:
- suppress the local sounder;
- activate the local sounder if
the fire extinguishing control
panel is in Fire condition
Stage I or Fault condition
and the local sounder has
been suppressed by
previous pressing of the
same button.
The button operation is
reversive i.e. press it once to
change the current condition
alternatively suppressed or
activated local sounder. The
LED indicator illuminates if the
active condition of the local
sounder is suppressed.
The local sounder is
activated again:
- when the fire