13.4.3.5. Setup Input Low Press
Due to the specificity of the input to
monitor the leaking of the extinguisher, the
active status for this function is OPEN
contact. it is provided the logic of the contact
to be turned in the case of not standard
installations as the active level could be with
Closed contact.
According to the standard this input
should function with active level OPEN
contact, otherwise the other option is an
exception.
The factory setting is active level with
OPEN contact.
Use the buttons (Down) and (Up) to change alternatively the parameter, the
button to confirm the new value and the button to exit.
13.4.4. Function Time Extinguishing
Use this function to set the time for
extinguishing. The specific value of the
parameter depends on the utilized automatic
devices. The factory setting is 10 seconds as
the admissible values are within the range
from 1 to 255 seconds.
The active buttons are and
- to reduce/increase the time for
extinguishing. To confirm the new value use
the button , to exit – press button .
13.4.5. Function Time Evacuation
Use this function to set the time for
evacuation The factory setting is 120 seconds
as the admissible values are within the range
from 1 to 255 seconds.
The active buttons are and - to
reduce/increase the time for evacuation. To
confirm the new value use the button ,
to exit – press button .