UniPOS Fire Extinguishing Control Panel FS5200Е
Instruction Manual Page 60
Revision 7/06.12 of 63
15. Labour protection requirements
The installation and maintenance staff shall be well grounded in equipment’s mechanism and
operation, as well as in common technical safety regulations.
Connection to unearthed or to indirectly earthing mains supply is prohibited.
Troubleshoots are to be cleared after disconnecting the feeding cable from the mains supply.
The fire extinguishing control panel is designed for installing in premises with a normal fire
hazard, as per the Fire Precaution Technical Regulations in Building Construction.
16. Fire extinguishing control panel start up
Make sure that the connection to mains power supply is properly made.
Make sure that the periphery devices are correctly connected.
Place the fuse in the terminal with mains fuse, the display illuminates and appears text message
with the name of the producer, the initials of the control panel and the software version. Then the
display shall show the current time and date.
Connect the feeding cable and the backup batteries; the batteries shall be in a series connection.
Connect the red wire to the positive backup battery pole, and the blue wire to the negative pole.
The overall voltage of both batteries shall not exceed 17.6V, otherwise the fire extinguishing control
panel will not recognize them.
Enter Set Up Mode and configure the common parameters and the lines parameters.
Upon exit of Set Up Mode the fire extinguishing control panel runs all system operations and
enters Duty Mode the control panel is ready to fire protect the site.
17. Operation, storage and transportation
17.1 Operation and storage
The fire extinguishing control panel shall operate and be kept in closed premises, under the
following conditions:
17.1.1. Temperature
storage - from 5С to 35C
transportation - from minus10С to 50C
operational - from minus 5С to 40С
17.1.2. Relative humidity
storage - to 80
operational - to 93
17.2. Transportation
The fire extinguishing control panel shall be transported by vehicles, in factory packing, in the
above stated environmental conditions and at sinusoidal vibrations with acceleration amplitude not
more than 4,9m/s
2
in frequency range 10 to 150Hz.
18. Warranty
The producer guarantees compliance of the device with EN 54-2:1997/ А1:2006/AC: 2009,
EN 54-4:1997/A2: 2006/AC: 2009, EN 12094-1: 2003. The warrant period is 18 months from the
date of the purchase, providing that
the conditions of storage and transportation have been observed;
the startup has been done by authorized personnel only
the requirements for operation stated herein have been observed.
UniPOS
47, “San Stefano” Str., 5800 Pleven, BULGARIA
phone +359 64 891111, +359 64 891 100, fax +359 64 891 110
e-mail: office_pleven@unipos-bg.com
Mladost 1, bl.79B, entr.2, ap.17, 1784 Sofia, BULGARIA
phone/fax +359 2 9744469, +359 2 9743925
e-mail: office_sofia@unipos-bg.com
www.unipos-bg.com

Table of Contents

Related product manuals