89
5 COMMUNICATIONS
89
COMMUNICATIONS
Chapter
5
- Set value write command (Work Setting)
Example: Writing “1000” to Y-axis Start Point, Display Range Setting, Work No. 10, Work Setting
① Writing “10” to Work No.
② Writing “1000” to Y-axis Start Point after Work No. is written normally
Host
(Transmission to the F381A)
Item No. (See the list of set value commands.)
Work No. in the example
Item group (See the list of set value commands.)
Work Setting in the example
00+0000010W1 0
Delimiter
Data to write
“10” in the example
F381A’s return
(In normal processing)
Command received by the F381A
Header (If there is no header, no data will result.)
(
STX
)
Delimiter
00W0 010+00 001
(
STX
)
Delimiter
N1G
F381A’s return
(In abnormal condition)
Header (If there is no header, no data will result.)
NG No.
1: Receipt of a statement different from the command format
2: Attempt to write a set value outside the setting range
4: Attempt to write a set value through communications
during measurement
5: Attempt to write while protecting
F381A’s return
(In normal processing)
Command received by the F381A
Header (If there is no header, no data will result.)
(
STX
)
Delimiter
10W2 010+00 000
Host
(Transmission to the F381A)
Item No. (See the list of set value commands.)
Y-axis Start Point in the example
Item group (See the list of set value commands.)
Display Range Setting in the example
00+0000100W1 2
Delimiter
Data to write
“1000” in the example
(
STX
)
Delimiter
N1G
F381A’s return
(In abnormal condition)
Header (If there is no header, no data will result.)
NG No.
1: Receipt of a statement different from the command format
2: Attempt to write a set value outside the setting range
4: Attempt to write a set value through communications
during measurement
5: Attempt to write while protecting